INSTALLATION A OFF 25A lDn 0.03A 20A Min. 3 x 1mm2 C ØMin:6,5 mm 2 According to current legislation ØMax: 8,5 mm2 B IPX4 D Included 240 VAC D 50 Hz. 17 W E A The electrical installation must be protected by means of a IDn 0,03A and 25A differential switch and a magnetothermal switch of 10 or 15A. Both switches must be placed outside the bathroom. B The power connection if this product must be permanently connected to a xed electricity line. Placement of a plug is not acceptable. The electrical line to be installed must be a exible cable consisting of three wires (active, neutral, earth) of at least C 1mm2of section exclusively dedicated to the WC. In the event that, due to failure, it is necessary to handle or replace the power cable, this must only be done by Technical Service staff. D The power connection must only be done inside the included IPX4 electrical box. In case of making a junction of the electrical line must be also used a box of this type. E The range of function of the WC is 240V, 50Hz. - Any electrical work conducted on this product must be installed only by qualified personnel, in accordance with AS/NZS 3000 Wiring Rules. Note - Please consult with a qualied electrician to conrm an appropriate installation location. - No additional electrical equipment should be tted inside the toilet. - This product (IPX4) shall not be exposed to water jets for cleaning purposes. 87