E2.1 Smart Toilets Installation®-WASH INSPIRAIN Wall-hung A 25A lDn 0.03A 10 ó 15A OFF According to current legislation 3 x 1mm2 Mandatory L Min. = 300 mm C ØMin: 6 mm ØMax: 8,5 mm B 240 VAC 50 Hz. 1700 W Max. D A The electrical installation must be protected by means of a IDn 0,03A and 25A differential switch and a magnetothermal switch of 10 or 15A. Both switches must be placed outside the bathroom. A fixed power connection must be connected by a dedicated flexible power cable consisting of 3 wires (active, B neutral,earth) of at least 1mm . The connection must be done inside an IPX42or better junction box. If it is necessary to replace the power cable, this must be done by qualified service staff. C 240V, 50 Hz. - Any electrical work conducted on this product must be installed only by qualified personnel, in accordance with AS/NZS 3000Wiring Rules. Note - Please consult with a qualified and licensed electrician to confirm an appropriate installation location. - No additional electrical equipment should be fitted inside the WC. - This product (IPX4) shall not be exposed to water jets for cleaning purposes. 126