A OFF 25A l D n 0.03A 20A 100-240 VAC 50/60 Hz. 17 W According to current legislation E Min. 3 x 1mm 2 C ØMin: 6,5 mm2 ØMax: 8,5 mm2 B IPX4 D Included V =Volume A The electrical installation must be protected by means of a IDn 0,03A and 25A differential switch and a magnetothermal switch of 20A. Both switches must be placed outside the bathroom. V B The power connection of this product must be permanently connected 1 to a fixed electricity line. Placement of a plug is not acceptable. C The electrical line to be installed must be a hose consisting on three F drivers (phase, neutral, earth) of at least 1mm2 of section exclusively dedicated to the WC. In the event that, due to failure, it is necessary to handle or replace the power cable, this must only be done by Technical V Service staff. 0 D The power connection must only be done inside the included IPX4 V electrical box. In case of making a junction of the electrical line must be 2 also used a box of this type. The range of function of the WC is 100-240V, 50/60Hz. V E The WC must be installed in the protection volume 3 of the bathroom. 3 FNeither component nor connection of the WC must be operated. No electrical device must be introduced inside the WC. This product must be installed by qualified personnel, in according with the national current regulation. 87 2250600 600