A OFF 25A l D n 0.03A 20A 100-240 VAC 50/60 Hz. According to current legislation 17 W E Min. 3 x 1mm 2 C ØMin: 6,5 mm2 ØMax: 8,5 mm2 B IPX4 D Included V =Volume A The electrical installation must be protected by means of a IDn 0,03A and 25A differential switch and a magnetothermal switch of 20A. Both switches must be placed outside the bathroom. B The power connection of this product must be permanently connected to a fixed electricity line. Placement of a plug is not acceptable. V C The electrical line to be installed must be a hose consisting on three 1 drivers (phase, neutral, earth) of at least 1mm2 of section exclusively F dedicated to the WC. In the event that, due to failure, it is necessary to handle or replace the power cable, this must only be done by Technical Service staff. V D The power connection must only be done inside the included IPX4 0 electrical box. In case of making a junction of the electrical line must be also used a box of this type. V The range of function of the WC is 100-240V, 50/60Hz. 2 E The WC must be installed in the protection volume 3 of the bathroom. V FNeither component nor connection of the WC must be operated. 3 No electrical device must be introduced inside the WC. This product must be installed by qualified personnel, in according with the national current regulation. 67 2250600 600